HXGN-12 type fixed metal-enclosed switchgear (hereinafter referred to as ring main unit) is a 12kV rated voltage, 50Hz rated frequency AC high-voltage complete electrical equipment, mainly used for three-phase AC ring network, terminal distribution network and industrial power equipment, for receiving and distributing electric energy, etc. It is also suitable for high-voltage installation.
Overview
The HXGN-12 box-type fixed metal-enclosed switchgear (hereinafter referred to as ring network cabinet) is a 12kV rated voltage, 50Hz rated frequency AC high-voltage complete electrical equipment, mainly used for three-phase AC ring networks, terminal distribution networks and industrial power equipment, for receiving and distributing power. It is also suitable for high-voltage installation.
Usage Environment Conditions
•Uses a full-set device structure, lightweight and beautiful, can be arbitrarily combined and installed, easy to infinitely expand and extend.
•Can be equipped with FKN12-12 type pneumatic indicating load switch, combination electrical appliance, or FZN25-12 type vacuum load switch, combination electrical appliance, and the installation dimensions are completely consistent. Small size, maintenance-free, three-phase linkage structure, and remote control function.
Manual and electric operation are available, and it has a remote control function.
It has a complete and reliable mechanical linkage and interlocking device, fully achieving the “five-prevention” function.
The load switch uses a linkage protective insulating valve to shield the energized handle, ensuring personal safety.
The front door is equipped with an observation window, which can clearly observe the working status of the components inside the cabinet.
Complies with GB3906, GB11022 and other standards.
Technical Parameters
| Serial Number |
Name |
Unit |
FKN12-12 |
FKRN12-12 |
|
| 1 |
Rated Voltage |
KV |
12 |
|
| 2 |
Imin Power Frequency Withstand Voltage |
KV |
Pole and phase 42, isolation port 48 |
|
| 3 |
Lightning Impulse Voltage (Peak) |
KV |
Pole and phase 75, isolation port 85 |
|
| 4 |
Rated Frequency |
Hz |
50 |
|
| 5 |
Main Busbar Rated Current |
A |
630 |
|
| 6 |
Rated Current |
A |
630 |
|
| 7 |
Load Switch |
Rated Electrical Life under Current |
Times |
No less than 100 |
| 8 |
Load Switch |
Breaking Capacity of No-load Transformer |
KVA |
1250, 1600 |
| 9 |
Load Switch |
Rated Thermal Stability Current |
KA/S |
20/4, grounding switch 20/2 |
| 10 |
Load Switch |
Rated Dynamic Stability Current (Peak) |
KA |
50 |
| 10 |
Load Switch |
Rated Short-circuit Closing Current (Peak) |
KA |
50 |
| 12 |
Combination Electrical Appliance |
Fuse Rated Current |
A |
100 |
| 13 |
Combination Electrical Appliance |
Rated Transfer Current |
A |
|
2000 |
| 14 |
Combination Electrical Appliance |
Rated Short-circuit Breaking Current |
KA |
31.5 |
| 15 |
Combination Electrical Appliance |
Matching Fuse Model |
|
SLAJ-12(XRNT-12) |
| 16 |
Mechanical Life |
Times |
3000 |
10000 |
|
| 17 |
Auxiliary Circuit Imin Power Frequency Withstand Voltage |
KV |
2 |
|
| 18 |
Electric Operating Mechanism Working Voltage |
V |
AC/DC 220, 110 |
|
| 19 |
Protection Level |
|
1P4X |
|
| 20 |
Dimensions (Width × Depth × Height) |
mm |
700 (900) × 900 × 2000 (2200) |
|
Ordering Instructions
Please provide the following information when ordering:
• Switchgear model, quantity, delivery date and primary scheme number;
• Primary system diagram, secondary principle diagram and switchgear arrangement diagram;
• Main busbar rated current and model and specifications of primary components;
• Special requirements (if any).